25 years ago today was the infamous Jomtien Hotel fire that killed over 90 people-here is the story

Jomtien, Thailand-

  25 years ago today, July 11th, 1997, a tragic fire in Jomtien at a hotel killed over 90 people, many of them tourists, and led to significant changes in both local fire departments, emergency response times, and hotel policies. Here is the story behind the event, as originally posted on our sister website, Pattaya Unplugged, and with some sourcing from Wikipedia:

The Royal Jomtien Resort Hotel Fire

From Wikipedia, with some light editing and additions from our team:

The Royal Jomtien Resort Hotel was a 450-room luxury hotel situated in a 17-story high-rise building on the northern end of Jomtien Beach, 110 kilometers (68 mi) south of Bangkok. At approximately 10:20 local time, 11 July 1997, a fire ignited as a result of a faulty liquid propane gas cylinder in a ground floor buffet of the hotel. The fire burned for 8 to 12 hours across all floors and caused the deaths of at least 102 people and injuries to a further 63.

A National Fire Protection Association report attributed the ignition of the fire to human error by a worker who had identified a faulty valve assembly on a gas cylinder in a ground-floor buffet; while attempting to shut off the valve, the worker inadvertently increased the flow of gas and caused an explosion. The combustible wood and vinyl furnishings of the establishment allowed the fire to develop rapidly, as did a lack of fire separation, compartmentation, and active suppression systems. As acrid smoke overcame the entire complex, several victims reportedly jumped from the higher windows to their deaths.

At the time of the fire, the building was 8 years old and had therefore been constructed prior to 1992 laws dictating mandatory installation of fire alarms and smoke detectors in Thai high-rise hotels.  The fire prompted a review of safety standards of other high-rise buildings in Chon Buri and at least 200 other buildings in the Pattaya area were found not to comply with the fire safety standards that had been violated by the Royal Jomtien Resort Hotel prior to the fire.

Details of the Fire

The source of the fire is thought to have been a liquid propane gas cylinder of 9 kilograms (20 lb) in size that was attached to an oven or other cooking appliance in a coffee shop — variously identified as a buffet — on the ground floor of the then 4-star hotel.

Sometime before 10:20 local time, employees of the ground-floor eatery noticed the smell of gas emanating from the kitchen. This initial release of gas was attributed to the actions of a kitchen helper — identified in the local media as Khayan Kasien — when he removed a hose from the cylinder without shutting off the valve.

According to a National Fire Protection Association report, a hotel worker — identified in the local media as Chamnien Suthho, the manager of the eatery — who had been investigating the smell attempted to shut off the valve on the cylinder and unwittingly increased the flow of vapor. The expanding vapor quickly ignited, causing a gas explosion that killed at least 8 workers in the kitchen. At the time of ignition, there were up to 300 guests inside the hotel complex.

Flames from the explosion quickly overwhelmed guests waiting in the lobby for breakfast. The combustible wooden and vinyl furnishings of the complex, a strong westerly breeze, and a lack of active fire suppression systems — such as sprinklers — allowed the fire to spread rapidly through the 1st level of the complex, and the entire lobby area was alight within 20 minutes. The 2nd level, which housed conference rooms that had been hosting seminars for Serm-Sukh PCL (partners of Pepsi Co. in Thailand) and Thailand’s electric authority (EGAT), was also fully alight within 30 minutes of ignition. Seminar attendees were heavily represented among the casualties of the fire, with at least 24 employees of EGAT identified among the dead.

A lack of pressurization in the stairwell, the absence of fire-stopping on service shafts, and few self-closers installed on upper-level doors had allowed toxic smoke to penetrate the 3rd to 16th floors and asphyxiate many of the people residing there. A particularly large number of fatalities occurred on the 11th floor, including those of several children.

The Response to the Fire

Inadequate fire training contributed to the initial spread of the fire; according to witnesses who spoke to The Nation, employees in the kitchen and coffee-house had failed to use one of the few chemical extinguishers appropriately and eventually left it to be consumed by the fire, causing a further explosion.

The official emergency response was delayed by connection issues and bureaucracy. According to the then guest relations manager of the hotel, she had attempted to call the Pattaya Fire Department and, after several issues, was only connected 15 minutes later. Witnesses who spoke to the Pattaya Times indicated the first emergency personnel had taken over 30 minutes to arrive, and the local firefighters that were in attendance lacked the appliances or equipment to reach people on the higher floors. Only two to four hours after ignition did appliances and equipment adequate for fighting fires in high-rise buildings arrive from Bangkok. The arrival of the Bangkok fire appliances was delayed in part by a traffic accident in Chachoengsao that killed 11 civilian volunteers who had also been traveling to the scene of the fire.

A trio of police helicopters that had flown in from Bangkok began retrieving victims stranded on the roof of the complex roughly 90 minutes into the emergency. An American tourist, Rochelle Stein Salmi, and her daughter were rescued from their 16th-floor room by a helicopter and featured prominently in subsequent media reports of the fire.

Rescue efforts were hindered by fire exits that had been blocked with stored equipment and padlocked from the outside; in one instance rescuers were forced to remove a padlock off one gate, which they reached only after clearing a path through hundreds of stored chairs. Emergency workers were also forced to use sledgehammers to break through a high perimeter fence for access to patients who required extraction to the hospital.

Deaths

Ninety-one guests died from burns, asphyxiation, thermal trauma, or jumping out of higher-level windows in an attempt to escape. The final fatality resulting from the fire was a 40-year-old woman who suffered serious burns and succumbed to a lung infection following a week-long coma. Among the victims were six Hungarians, three South Koreans, and one Belgian as well as dozens of Thai hotel employees, conference attendees, and tourists.

The practice of locking emergency exit doors to prevent guests from leaving without paying their bills greatly increased the number of casualties. The locked emergency exits were observed by numerous witnesses, including a guest and employee of EGAT, who offered the following footage to Reuters:

 

TPN media offers our condolences to the family and friends of those killed in the fire.

Subscribe
Adam Judd
Mr. Adam Judd is the Co-owner of TPN Media since December 2017. He is originally from Washington D.C., America, but has also lived in Dallas, Sarasota, and Portsmouth. His background is in retail sales, HR, and operations management, and has written about news and Thailand for many years. He has lived in Pattaya for over nine years as a full-time resident, is well known locally and been visiting the country as a regular visitor for over a decade. His full contact information, including office contact information, can be found on our Contact Us page below. Stories please e-mail Editor@ThePattayanews.com About Us: https://thepattayanews.com/about-us/ Contact Us: https://thepattayanews.com/contact-us/